|
Description  |
|
|
BACKGROUND OF THE INVENTION
1. Field of the Invention
The invention relates to the method and system for recovering polluted
water, especially for treating ground water and industrial wastewater
polluted by organic chlorine compounds.
2. Description of the Prior Art
In case ground water is used as industrial water, etc., it can not be used
without being treated if it is polluted. Although there are many causes of
polluting ground water, recently pollution of ground water with organic
chlorine compounds due to percolation of industrial wastewater into soil
is often reported.
As conventional methods for treating organic chlorine compounds e.g.
trichloroethylene, tetrachloroethylene and 1,1,1-trichloroethane,
contained in ground water, etc., there are evapotranspiration-adsorption
process (combination of heated aeration and activated carbon adsorption)
and oxidation decomposition process in which potassium permanganate and
Fenton's reagent are added into the water. But the most commonly employed
method in these days is the evapotranspiration-adsorption process which is
a combined method of heated aeration and activated carbon adsorption.
However, in heated aeration and activated carbon adsorption methods, which
form the evapotranspiration-adsorption process, activated carbon gets wet
due to water vapor generated in the aeration, resulting in considerable
capacity reduction of activated carbon for adsorbing organic chlorine
compounds. As a result, an amount of the compounds, which are not adsorbed
by activated carbon and thus released into the atmosphere, will increase.
The released compounds will percolate again into soil. Also, since the
saturated activated carbon must be disposed of, an extra cost for
disposing the activated carbon is required. In addition, there are other
problems including clogging of piping, heat exchanger and diffuser pipe
caused by propagation of bacteria in the section where ground water is
transferred, heated and aerated. On the other hand, in the oxidation
decomposition process using potassium permanganate and Fenton's reagent,
etc., consumption of reagent is large, and after-treatment of the treated
water is required because the pollutant load is increased due to the use
of the reagent and also because heavy metals are contained in the reagent.
OBJECT AND SUMMARY OF THE INVENTION
An object of the invention is to provide the method for effectively
recovering polluted water, especially polluted ground water and industrial
wastewater.
Another object of the invention is to provide the method for recovering
water polluted by organic chlorine compounds.
A further object of the invention is to provide the method for recovering
polluted water by effectively removing bacteria, suspended solid and
organic chlorine compounds from water.
A still further object of the invention is to provide the method for
recovering polluted water only by addition of oxidizing agent into
polluted water followed by ultraviolet rays irradiation and also by
reduction of residual oxidizing agent as after-treatment.
A still further object of the invention is to provide the method for
recovering polluted water by adequately controlling pH and temperature of
raw water.
A still further object of the invention is to provide the system for
implementing the methods mentioned above.
Further objects and advantages of the invention will be apparent from the
following description of the invention.
Recovery of polluted water based on the invention is achieved by carrying
out disinfection, removal of suspended solid, decomposition of organic
chlorine compounds and treatment of residual oxidizing agent in its order.
In addition, after the removal of suspended solid, pH and temperature of
raw water is adjusted prior to decomposition of organic chlorine
compounds. The system for carrying out the above-mentioned processes is
formed of a disinfection unit, a filter, an UV-oxidation-decomposition
unit and a reduction unit, and also pH and temperature adjustment units
are used, as required.
BRIEF DESCRIPTION OF THE DRAWINGS
FIG. 1 shows a system based on the invention.
FIGS. 2 and 3 indicate relation between trichloroethylene concentration and
ultraviolet rays irradiation amount.
FIG. 4 indicates relation between pH and residual trichloroethylene
concentration for the same amount of ultraviolet rays irradiation.
FIG. 5 indicates relation between trichloroethylene concentration and
ultraviolet rays irradiation amount for various raw water temperatures.
DETAILED DESCRIPTION OF PREFERRED EMBODIMENT
The first process, conducted in accordance with the invention, is a
disinfection process. In the process, bacteria, which propagates due to
various organic materials contained in polluted ground water, etc., is
disinfected by oxidizing agent such as hydrogen peroxide and ozone. As a
result of this, clogging of flowmeter, filter and piping used in the
treatment system can be prevented. Oxidizing agents used in this process
are not necessarily limited to special types, but should preferably
satisfy such requirements as strong bactericidal action, high ultraviolet
rays absorption capacity, easy after-treatment and having no corrosiveness
on piping. Ozone is almost insoluble in water and thus inefficient in
disinfection. Further, ozone, which has not been dissolved in water,
causes offensive smell. By contrast, hydrogen peroxide can be easily
handled, and residual hydrogen peroxide in water can be easily decomposed
into water and oxygen by using ultraviolet rays, reducing agent and
activated carbon. As to the amount of oxidizing agent to be added to the
water, it is determined by taking into account both the disinfection
effect and the amount required for decomposing organic materials conducted
in the organic chlorine compound decomposing process in the 5th process.
In the 2nd process, suspended material is removed from the water by either
filtration or sedimentation.
In the 3rd process, pH of the water treated in the 1st and 2nd processes is
adjusted to 9 or below--preferably between 3 and 9.
In the 4th process, temperature of the water treated in the 3rd process is
adjusted to fall within a range of 15.degree. to 30.degree. C.
The 3rd and 4th processes are the precesses required depending upon the
condition of the water. Therefore, if the water satisfies the
above-mentioned requirements, they are not necessary.
In the 5th process, organic chlorine compounds are oxidation-decomposed by
irradiating ultraviolet rays on residual oxidizing agent remaining in the
water treated in the 1st, 2nd, 3rd and 4th processes. In the oxidation
decomposition reaction, the organic chlorine compounds are
oxidation-decomposed by active oxygen generated by irradiating ultraviolet
rays on the residual oxidizing agent. As a result of the
oxidation-decomposition reaction, water, carbon dioxide and trace
hydrochloric acid are generated. If necessary, the hydrochloric acid is
then adsorbed by weak ion exchange resin. As UV lamp, either high pressure
or low pressure mercury lamps may be used, but if hydrogen peroxide is
used as oxidizing agent, a low pressure mercury lamp is advantageous
because it irradiates ultraviolet rays with a main wave length of 253.7 nm
which can efficiently decompose the oxidizing agent.
In the 6th process, the residual oxidizing agent carried over from the 5th
process is reduced by using reducing agent, activated carbon or catalyst
resin. For example, in case of hydrogen peroxide, it is reduced to oxygen
and water. While, in case of ozone, it is reduced to oxygen.
Further, in the 5th process, when an organic chlorine compound is
oxidation-decomposed, hydrochloric acid is formed. Especially, in case the
concentration of the compound is high, pH of the water will drop
considerably. In this case, the oxidation decomposition is carried out by
adjusting pH of the water by adding alkali to the water in the 5th process
or between the 5th and 6th processes. As alkali to be used for this
purpose, any alkali among potassium hydroxide, calcium hydroxide, sodium
hydroxide and sodium carbonate may be used. However, sodium hydroxide can
be most easily handled in operation.
Compared with the conventional methods, in the treatment method based on
the invention, organic chlorine compounds in polluted water can be easily
treated, and also propagation of bacteria, which results in the clogging
of piping can be avoided.
Moreover, the UV-oxidation-decomposition can be effectively carried out by
adjusting both pH and temperature of water to 9 or below and to a range of
15.degree. to 30.degree. C. respectively prior to the
UV-oxidation-decomposition process in the fifth process.
EXAMPLE
The examples of the invention are explained herein through the treatment
tests of the wastewater containing trichloroethylene. The treatment tests
were performed using the test equipment depicted in FIG. 1. Table 1
indicates the specification for the equipment.
TABLE 1
______________________________________
Specification of test equipment
Process Unit Specification
______________________________________
1st Disinfection 30% hydrogen peroxide
2nd Filtration 10.mu. cartridge filter
3rd pH adjusting 2% sodium hydroxide
10% sulfuric acid
4th Temp. adjusting
Heat exchanger
5th UV oxidation Capacity: 3.2 liters
degradation Material: Stainless steel
Jacket material: Quartz
Type of lamp: Low pressure
mercury lamp
Capacity: 30W
6th Reduction 10% sodium hydrogen sulfite
pH adjustment
2% sodium hydroxide
______________________________________
Guaranteed reagent of trichloroethylene was initially dissolved in pure
water in a measuring flask and put into tank 1, and then diluted with pure
water until the volume of the diluted solution reaches 20 liters. The
solution had a trichloroethylene concentration ranging from 5.0 to 0.05
mg/l and had 100 pcs/ml of live microorganism, and was used as a test
solution.
Using pump 2, the test solution was passed through cartridge filter 3 and
stored in tank 4. At the same time, hydrogen peroxide was supplied from
hydrogen peroxide storage tank 9 to tank 1 by pump 10. The hydrogen
peroxide concentration in tank 4 was adjusted to approx. 300 mg/l.
The hydrogen peroxide-containing test solution stored in tank 4 was
transferred by pump 5, via flowmeter 6 and heat exchanger 15, to
UV-oxidation-decomposition unit 7 where trichloroethylene is
oxidation-decomposed. FIGS. 2 and 3 show the measurement results for
trichloroethylene at initial concentrations of 5.0 mg/l and 0.05 mg/l
respectively.
In either of both tests, residual hydrogen peroxide in the test solution
was reduced by sodium hydrogen sulfite which had been supplied from sodium
hydrogen sulfite storage tank 11 to tank 8 by pump 12. At the same time,
sodium hydroxide was supplied to tank 8 to adjust pH of the test solution
lowered due to the oxidation decomposition. Sodium hydroxide was supplied
from sodium hydroxide storage tank 13 to tank 8 by pump 14.
As to disinfection which is one of the effects expected by applying the
invention, the disinfection effect by hydrogen peroxide could be confirmed
from the measurement results (0 pc/ml) of live microorganism in the test
solution sampled from tank 4. In addition to the above mentioned tests
carried out with hydrogen peroxide concentration adjusted to 300 mg/l, the
same tests were conducted with hydrogen peroxide concentration adjusted to
1000 mg/l, 500 mg/l and 100 mg/l, and no live microorganism was found in
any of the four test results.
The results of the trichloroethylene decomposition tests were shown in
FIGS. 2 and 3. The target value of the trichloroethylene concentration in
the treated water was set at 0.03 mg/l or less which is the provisional
standard value for city water (established by the Ministry of Health and
Welfare of Japan on Feb. 18, 1984). FIG. 2 shows the change of
trichloroethylene concentration in the water with respect to the quantity
of UV irradiation (kw.h/m.sup.3), which indicates the results of tests in
which trichloroethylene was decomposed by UV+H.sub.2 O.sub.2 precess
(based on the invention). That is, when the quantity of UV irradiation is
0.18 kw.h/m.sup.3, the trichloroethylene concentration in the treated
water becomes 0.5 mg/l. As the quantity of UV irradiation increases to
0.37, 0.77, 1.35 and 2.03 kw.h/m.sup.3, the trichloroethylene
concentration decreases to 0.04, 0.01, 0.004 and 0.003 mg/l. From the
results described above, it can be noticed that the treatment method based
on the invention is effective when the quantity of UV irradiation is
approx. 0.4 kw.h/m.sup.3 or above. FIG. 3 shows the results of the tests
conducted with an initial trichloroethylene of 0.05 mg/l. From the results
showing that the trichloroethylene concentration after being treated by UV
irradiation of 0.2 kw.h/m.sup.3 or above was 0.03 mg/l or less, it is
clear that the invention is effective. Especially, when the water was
treated by UV irradiation of 0.77 kw.h/m.sup.3 or above, the
trichloroethylene concentration fell down to below 0.001 mg/l.
For the application examples mentioned above, explanations were given only
to the cases where the initial trichloroethylene concentrations was 5.0
mg/l and 0.05 mg/l. However, even if the initial trichloroethylene
concentration was 5.0 mg/l or above or 0.05 mg/l or below, the
trichloroethylene concentration in the treated water could be easily
reduced to the target value of 0.03 mg/l or less.
Furthermore, as organic chlorine compounds contained in raw water, besides
trichloroethylene, there are tetrachloroethylene and
1,1,1-trichloroethane, and the pollution of ground water by the compounds
is becoming a serious problem. Therefore, decomposition tests were
conducted using the water containing 1.0-100 mg/l of tetrachloroethylene
and 1.0-100 mg/l of 1,1,1-trichloroethane as raw water, in the same manner
and under the same conditions as in the above mentioned case of
trichloroethylene. From the test results, it was confirmed that the
concentrations of the compound(tetrachloroethylene and
1,1,1-trichloroethane) in the treated water could be reduced down to 0.01
mg/l and 0.3 mg/l respectively. The target values of the concentrations of
tetrachloroethylene and 1,1,1-trichloroethane in the treated water were
set at the provisional standard values of city water (established by the
Ministry of Health and Welfare of Japan on Feb. 18, 1984.).
Furthermore, the effectiveness of both the pH adjusting process in the 3rd
process and the temperature adjusting process in the 4th process is
described below.
In tank 4 containing the water with 10 mg/l of trichloroethylene, pH of the
water was adjusted to 3, 5.3, 8, 9, 10 by adding sodium hydroxide and
sulfuric acid from sodium hydroxide storage tank 13 and sulfuric acid
storage tank 16 respectively to tank 4. The chemicals were added to the
solution in tank 4 so that the hydrogen peroxide concentration became 250
mg/l. Then, oxidation decomposition was carried out by means of
UV-oxidation-decomposition unit 7. FIG. 4 shows the measurement results of
the residual trichloroethylene concentration in case where the quantity of
UV irradiation was 0.77 kw.h/m.sup.3. When pH of the water was 3, 5.3, 8,
9, the residual trichloroethylene concentration in the treated water
became 0.003, 0.005, 0.004, 0.006 mg/l respectively. On the other hand,
when pH was 10, the residual trichloroethylene concentration became 0.14
mg/l, which proves the effectiveness of the invention.
In addition, different tests were conducted with trichloroethylene
concentration adjusted to 10 mg/l and hydrogen peroxide concentration to
220 mg/l respectively in tank 4. As test 1, the water in tank 4 was passed
through flowmeter 6 (at a flowrate of 0.6 l/min) and heat exchanger 15 to
adjust the water temperature to 10.degree. C., and then directed to
UV-oxidation-decomposition unit 7. Other tests were also carried out with
the water temperature at the heat exchanger outlet adjusted to 15.degree.,
22.degree., 30.degree. and 38.degree. C. as tests 2, 3, 4 and 5. As shown
in FIG. 5, when the quantity of UV irradiation was 0.77 kw.h/m.sup.3, the
residual trichloroethylene concentration in the treated water became 0.09
mg/l in test 1, 0.007 mg/l in test 2(water temperature: 15.degree. C.),
0.005 mg/l in test 3(water temperature: 22.degree. C.), 0.006 mg/l in test
4(water temperature: 30.degree. C.), 0.03 mg/l in test 5(water
temperature: 38.degree. C.). From the test results, it is clear that the
water temperature between 15.degree. to 30.degree. C. is effective in the
oxidation decomposition.
In the application examples mentioned above, the tests were performed with
an initial trichloroethylene concentration set at 10 mg/l in tank 4.
However, it has been confirmed that the oxidation decomposition under the
above mentioned conditions can be efficiently carried out at either higher
and lower concentrations. Needless to say, if pH of the water is 9 or
below and the temperature of the water is within a range of 15.degree. to
30.degree. C. in tank 4, the pH adjusting unit in the 3rd process and the
temperature adjusting unit in the 4th process may be naturally omitted.
In the treatment method based on the invention, in which the disinfection
of bacteria and the decomposition of organic chlorine compounds occur by
irradiating ultraviolet rays on the polluted water after the addition of
oxidizing agent to the water, polluted water can be effectively and
economically treated because only the reduction treatment of oxidizing
agent is required as the after-treatment of the treated water. In
addition, since bacteria can be disinfected by the addition of oxidizing
agent, clogging of piping, heat exchangers, etc. can be prevented only by
installing the suspended material removing process such as filtration and
sedimentation, which enables the system to treat and makes an effective
use of a large amount of polluted water including ground water.
Further, it is important for effective oxidation decomposition to adjust pH
of the water to 9 or below--preferably between 3 to 9, and to adjust the
temperature of the water within a range of 15.degree. to 30.degree. C. at
the inlet of the UV-oxidation-decomposition unit.
* * * * *
|
|
|
|
|
Description  |
|